IG-55 (Argonite) Inert Gas Suppression System
IG-55 (Argonite) is a CO2-free inert gas suppression agent made of 50% nitrogen and 50% argon; it extinguishes fire by lowering ambient oxygen below the level needed to sustain combustion, without damaging electronics or sensitive materials.
- Agent family
- Inert gas (50% N₂, 50% Ar)
- Storage
- Compressed gas (150, 200 or 300 bar at 15 °C)
- Extinguishing action
- Oxygen dilution
- Occupied spaces
- Suitable: same NFPA 2001 limits as IG-541
Our engineers respond within 24-48 hours.
Technical summary
| Property | Value |
|---|---|
| Agent family | Inert gas (50% N₂, 50% Ar) |
| Storage | Compressed gas (150, 200 or 300 bar at 15 °C) |
| Extinguishing action | Oxygen dilution |
| Occupied spaces | Suitable: same NFPA 2001 limits as IG-541 |
| GWP | 0 |
| Cylinder space needed | Large |
| Standards and approvals | TPED, PED, CE, UL, LPCB |
What Is It?
IG-55, marketed as Argonite, is a carbon-dioxide-free inert gas suppression agent made of 50% nitrogen and 50% argon. Like IG-541, it works through a physical mechanism rather than a chemical reaction, lowering the ambient oxygen level in the protected space to a point where fire can no longer be sustained. Its system components — cylinder bank, manifold, discharge valves, pipe network, nozzles, control panel, and detection units — share largely the same engineering platform as IG-541 systems.
The difference between IG-55 and IG-541 is that IG-55’s blend contains no CO2. Both extinguish by diluting oxygen, and the oxygen level in the room is set by the chosen design concentration, not by the agent. The U.S. EPA lists both as acceptable under NFPA 2001, and the same concentration and exposure-time limits apply to both in occupied spaces.
How It Works
When the detection units confirm a fire, the control panel triggers the discharge valve; the gas mixture, stored as a gas at 150, 200 or 300 bar (at 15 °C), is routed through the manifold and pipe network to the nozzles and distributed through the space on the total flooding principle. In many systems a pressure-reducing device after the cylinder valve limits the pipework pressure. System components are designed for reliable operation across an ambient temperature range of -20°C to +50°C. The gas’s volumetric spread also reaches shadowed areas such as behind equipment housings and racks.
After discharge, the low-oxygen atmosphere must be held for a set hold time, which depends on the sealing level of the protected space and is verified through door-fan testing. Because discharge briefly raises the pressure in the room, a pressure relief vent suited to the room construction is also calculated.

Where It’s Used
IG-55 is used in data centers and their support areas, control and electrical rooms in industrial facilities, switchgear and equipment rooms in power plants, and technical spaces in transport infrastructure such as metro and airport facilities.
Leaving no residue and being electrically non-conductive makes IG-55 suitable for technical spaces with sensitive hardware. Local agent supply and refill options, the system manufacturer’s approvals and cylinder space usually decide between IG-55 and IG-541.
Safety
Whether IG-55 can be used in an occupied space depends on keeping the design concentration within the NFPA 2001 limits for inert gases: up to 43% concentration (about 12% oxygen) for no more than 5 minutes, 43-52% (about 12-10% oxygen) for no more than 3 minutes; higher concentrations are used only in normally unoccupied spaces. The same limits apply to IG-541.
System reliability depends on a correctly sized cylinder bank, regular pressure monitoring, and periodic room integrity testing. Making sure that anyone who might be in the space during or after discharge is alerted by the alarm, with clearly defined evacuation procedures, is an integral part of the system’s safety design.
The Inert Gas Family and Technology
IG-55 (Argonite) belongs to the inert gas family, which extinguishes by diluting oxygen. To compare IG-01, IG-100, IG-55 and IG-541 by composition, standards and density, see our inert gas fire suppression systems guide; for the technology we use in our inert gas systems, see our Fire Eater page.
Advantages and limitations
| Advantages | Limitations / points to watch |
|---|---|
| CO2-free, pure nitrogen/argon blend | Contains no CO2; in occupied spaces the concentration and exposure time must be calculated to the NFPA 2001 limits |
| Leaves no residue; does not damage electronics or sensitive equipment | Requires more cylinders/storage volume than chemical agents at the same working pressure |
| Three-dimensional, volumetric distribution reaches shadowed areas | Effectiveness depends on tight room integrity, verified by door-fan testing |
| Negligible environmental impact due to its naturally occurring gas composition | — |
| Electrically non-conductive | — |
| Can be used in occupied spaces within the NFPA 2001 concentration and exposure-time limits for inert gases | — |
Downloads
Frequently asked questions
What's the key difference between IG-55 (Argonite) and IG-541?
Can IG-55 be used in a continuously occupied space?
Can an IG-55 system share equipment with an existing IG-541 installation?
What kinds of facilities typically use IG-55?
Does IG-55 damage electronic equipment or sensitive materials?
This system is one of the gas fire suppression systems GYS designs and installs. Comparisons with other agents, applications and the project process are on our home page.
Sources
- ISO 14520-14:2015 — Gaseous fire-extinguishing systems, Part 14: IG-55 extinguishant (150, 200 and 300 bar at 15 °C)
- U.S. EPA — SNAP: Substitutes in Total Flooding Agents (IG-541, IG-55, IG-01, IG-100)
- NFPA 2001, 2024 revision cycle public input responses — inert gas concentration and exposure time clause
Information Needed for a Quote
- Net dimensions of the protected space and ceiling height
- Occupancy profile of the space (continuously occupied, or predominantly unoccupied technical area)
- Room integrity/sealing condition and existing openings
- Existing detection and control panel infrastructure
- Whether the project needs single-zone (stand-alone) or multi-zone protection
- Location and size of the technical area available for the cylinder bank

Is this system right for your project?
Share the size of the space, whether people are present, and the room you can allocate for cylinders. Our engineers will assess the agent and system architecture and get back to you.