NOVEC 1230 clean agent suppression cylinder in a data center corridor

Products

FK-5-1-12 (Novec 1230) Clean Agent Suppression System

FK-5-1-12 is a fluoroketone-based clean agent that discharges in under 10 seconds and carries an exceptionally low environmental footprint (GWP of 1, atmospheric lifetime of about 5 days); because its design concentration is calculated below its NOAEL (10%), it can be used in occupied spaces together with a pre-discharge alarm and evacuation procedure.

Agent family
Chemical clean agent (fluoroketone)
Storage
Liquid, nitrogen-pressurized (25–50 bar)
Extinguishing action
Mainly heat absorption
Occupied spaces
Suitable: design concentration below the NOAEL (10%), with alarm and evacuation

Our engineers respond within 24-48 hours.

Technical summary

PropertyValue
Agent familyChemical clean agent (fluoroketone)
StorageLiquid, nitrogen-pressurized (25–50 bar)
Extinguishing actionMainly heat absorption
Occupied spacesSuitable: design concentration below the NOAEL (10%), with alarm and evacuation
GWP1
Cylinder space neededSmall
Standards and approvalsTS EN 15004, ISO 14520, NFPA 2001, TPED, PED, CE, UL, FM, LPCB

What Is It?

FK-5-1-12, best known under the trade name 3M™ Novec™ 1230, is a clean suppression agent based on a fluoroketone (C6F12O). Used against Class A, B, and C fires, it extinguishes by interrupting the fire’s heat transfer through a combination of chemical and physical action. The system is built around pressurized FK-5-1-12 cylinders, pipe network, nozzles, a control panel, and detection units, engineered specifically for the protected volume.

What most clearly sets FK-5-1-12 apart from FM-200 is its global warming potential: it has a GWP of 1 and an atmospheric lifetime of about 5 days. That is the lowest GWP among chemical clean agents; inert gases, made of naturally occurring gases, have a GWP of zero. Because its design concentration is calculated below its NOAEL (10%), it can also be used in occupied spaces, again with a pre-discharge alarm and evacuation procedure.

How It Works

When the detection units confirm a fire, the control panel triggers the discharge valve; liquid FK-5-1-12, pressurized with nitrogen in the cylinder, is delivered through the pipe network to the nozzles, where it vaporizes and fills the space in under 10 seconds. The agent extinguishes mainly by absorbing heat. System pressure (25, 34.5, 42 or 50 bar under ISO 14520-5:2024) and the operating temperature range are taken from the approval documents of the system used.

As with other clean agents, FK-5-1-12’s effectiveness depends on holding the design concentration for the required hold time after discharge. The sealing level of the protected space is therefore verified with door-fan testing, and pipe network and nozzle selection are calculated to ensure even distribution across the entire volume.

Novec 1230 (FK-5-1-12) clean agent suppression control panel

Where It’s Used

FK-5-1-12 is the preferred choice for occupied spaces, or spaces where environmental impact ranks high among the project’s design criteria: data centers and server rooms, museum and archive storage, critical infrastructure in hospitals and hotels, technical rooms in office buildings, and electrical/telecom spaces in shopping and mixed-use centers are the primary applications.

Its low GWP makes FK-5-1-12 a standout choice specifically on corporate projects with sustainability targets or environmental reporting obligations.

Safety

In the U.S. Environmental Protection Agency’s SNAP review, FK-5-1-12 is given a no observed adverse effect level (NOAEL) of 10% by volume. In occupied spaces the design concentration is calculated to stay below this value. As with any clean agent system, an audible and visual alarm sounds before discharge, the space is evacuated during the defined delay, and unnecessary exposure is avoided. Because the agent can form decomposition products when exposed to high temperatures in a fire, the space should not be re-entered after discharge until it has been ventilated and an authorized person has cleared it.

The system’s long-term reliability depends on correct pipe network design, periodic hydrostatic testing, and regular room integrity checks. A planned maintenance schedule after commissioning ensures both the extinguishing performance and the environmental advantages hold up over the life of the project.

Supply Status

In December 2022, 3M announced it would exit PFAS manufacturing by the end of 2025, and it has discontinued its Novec™ product family as part of that exit. “Novec 1230” is a trade name; the chemical name of the agent is FK-5-1-12, and it is also produced by other manufacturers. For new projects and for refilling existing systems, the agent and manufacturer the system is listed/approved with should be confirmed from the system manufacturer’s documentation.

EU PFAS Restriction

FK-5-1-12 is among the substances covered by the universal PFAS restriction proposal submitted to the European Chemicals Agency (ECHA) in January 2023; the same proposal also covers HFC-227ea (FM-200). According to the July 2024 assessment by the industry association Eurofeu, the proposal foresees an 18-month transition after entry into force plus a 12-year derogation for clean fire suppressant agents. Eurofeu also reports that ECHA confirmed in a meeting that there is, for now, no intention to restrict the use and refilling of existing systems. The proposal is still under committee review and no ban is in force. For long-lived installations, including projects in Türkiye, we recommend following this process.

Advantages and limitations

AdvantagesLimitations / points to watch
Global warming potential (GWP) of 1 — the lowest among chemical clean agents (inert gases have a GWP of zero)Within the scope of the EU universal PFAS restriction proposal; the transition period for fire suppression use is still under assessment
Atmospheric lifetime of about 5 daysReaching design concentration requires tight room integrity and door-fan testing
Wide safety margin between design concentration and NOAEL (10%)Correct engineering calculation and pipe network design are essential for effective protection
Fast response with discharge times under 10 secondsRequires periodic hydrostatic testing and refill infrastructure
Leaves no residue after discharge; does not damage sensitive equipment—
25, 34.5, 42 or 50 bar pressure options, depending on the system manufacturer—

Downloads

All downloads →

Frequently asked questions

What is the environmental impact of FK-5-1-12 (Novec 1230)?
FK-5-1-12 has a global warming potential (GWP) of 1 and an atmospheric lifetime of about 5 days — the lowest GWP among chemical clean agents. Inert gases, made of naturally occurring nitrogen and argon, have a GWP of zero. FK-5-1-12 is also within the scope of the EU universal PFAS restriction proposal; according to the industry association Eurofeu, its main degradation product, trifluoroacetic acid (TFA), is persistent. The proposal is still under assessment.
Is FK-5-1-12 safe for use in occupied spaces?
Yes, under defined conditions. FK-5-1-12 has a no observed adverse effect level (NOAEL) of 10% by volume, and the design concentration is calculated to stay below it, so it can be used in occupied spaces such as data centers, offices and museums. Even so, an audible and visual alarm sounds before discharge, the space is evacuated during the delay period, and unnecessary exposure is avoided.
How fast does FK-5-1-12 extinguish a fire?
Once triggered, liquid FK-5-1-12 vaporizes and fills the protected space in under 10 seconds, reaching the design concentration needed to interrupt the fire's heat transfer mechanism.
What system pressures are available for FK-5-1-12 installations?
FK-5-1-12 is stored as a liquid and pressurized with nitrogen. ISO 14520-5:2024 covers systems with nominal pressures of 25, 34.5, 42 and 50 bar. The pressure used depends on the system manufacturer's approved range, the pipe run length and the distance between the cylinders and the protected room.
Why is FK-5-1-12 often chosen for museums and data centers?
It leaves no residue after discharge and doesn't damage sensitive equipment, making it a safe choice for spaces with valuable electronics or collections. Its low GWP also makes it stand out on corporate projects with sustainability targets or environmental reporting requirements.

This system is one of the gas fire suppression systems GYS designs and installs. Comparisons with other agents, applications and the project process are on our home page.

Sources

  1. U.S. EPA, Federal Register Vol. 67, 20 Dec 2002 — SNAP Notice 17 (C6-perfluoroketone / FK-5-1-12)
  2. U.S. EPA, Federal Register Vol. 68, 27 Jan 2003 — SNAP listing (HFC-227ea: NOAEL 9.0%, LOAEL 10.5%; C6-perfluoroketone: NOAEL 10%)
  3. 3M News Center, 20 Dec 2022 — 3M to Exit PFAS Manufacturing by the End of 2025
  4. ISO 14520-5:2024 — Gaseous fire-extinguishing systems, Part 5: FK-5-1-12 extinguishant (25, 34.5, 42 and 50 bar)
  5. Eurofeu, July 2024 — FAQ PFAS and halocarbon gaseous fire extinguishing agents

Information Needed for a Quote

  • Net dimensions of the protected space and ceiling height
  • Occupancy profile of the space (continuous vs. intermittent occupancy)
  • Room integrity/sealing condition
  • Where the cylinders will stand and their distance from the protected room
  • How much weight environmental/sustainability priorities carry in the project
  • Existing detection and control panel infrastructure

Is this system right for your project?

Share the size of the space, whether people are present, and the room you can allocate for cylinders. Our engineers will assess the agent and system architecture and get back to you.