Types of Gas Fire Suppression Systems

The extinguishing gases and panel/detection solutions used in gas fire suppression systems, each engineered to a specific risk profile through hydraulic calculation.

Pages in this section

Close-up of an FM-200 suppression system valve manifold and pressure gauges
FM-200

FM-200 (HFC-227ea) Clean Agent Suppression System

FM-200 (HFC-227ea) is a colorless, odorless, electrically non-conductive clean agent that discharges in under 10 seconds and extinguishes fire mainly by absorbing heat; with its design concentration calculated below human-safety limits, it can be used in occupied spaces together with a pre-discharge alarm and evacuation procedure.

NOVEC 1230 clean agent suppression cylinder in a data center corridor
FK-5-1-12

FK-5-1-12 (Novec 1230) Clean Agent Suppression System

FK-5-1-12 is a fluoroketone-based clean agent that discharges in under 10 seconds and carries an exceptionally low environmental footprint (GWP of 1, atmospheric lifetime of about 5 days); because its design concentration is calculated below its NOAEL (10%), it can be used in occupied spaces together with a pre-discharge alarm and evacuation procedure.

Labeled INERGEN IG-541 cylinder bank and manifold line
IG-541

IG-541 (Inergen) Inert Gas Suppression System

IG-541 (Inergen) is a natural inert gas blend of 52% nitrogen, 40% argon, and 8% carbon dioxide that extinguishes fire by lowering ambient oxygen to a level that can no longer sustain combustion, while remaining breathable for a limited time; its CO2 component stimulates respiration, but the space is still alarmed and evacuated before discharge.

Inert gas fire suppression system cylinder room
IG-55

IG-55 (Argonite) Inert Gas Suppression System

IG-55 (Argonite) is a CO2-free inert gas suppression agent made of 50% nitrogen and 50% argon; it extinguishes fire by lowering ambient oxygen below the level needed to sustain combustion, without damaging electronics or sensitive materials.

CO2 gas fire suppression cylinder bank and wall-mounted control panel
CO2

CO2 Gaseous Fire Suppression System

A CO2 gaseous fire suppression system is a high-pressure total flooding system that extinguishes Class A, B, and C fires by lowering the oxygen level in an enclosed space below the point where combustion can continue; because that concentration is dangerous to breathe, CO2 is used only in unoccupied or evacuated spaces.

Electrical cabinet gas suppression cylinder and open enclosure

In-Cabinet Gaseous Suppression System

An in-cabinet gaseous suppression system is a compact unit installed directly inside an electrical panel or equipment cabinet, triggered by a pressurized polymer detection tube that bursts at roughly 100–110°C; it discharges FM-200, Novec 1230, or CO2 right at the heat source without needing a separate electronic detection system.

Close-up of a ceiling-mounted smoke detector

Fire Detection Systems

A fire detection system evaluates signals from heat, smoke (visible/invisible), and flame detectors on a zone-by-zone basis and triggers automatic gaseous suppression through the control panel; it is the trigger layer of a suppression system and does not extinguish fire on its own.

Technical comparison of the agents

Values summarize the sourced information on our product pages. Exact figures are taken from the approval documents of the system used on the project.

SystemAgent familyStorageExtinguishing actionOccupied spacesGWPCylinder space
FM-200 (HFC-227ea)Chemical clean agent (HFC)Liquid, nitrogen-pressurized (typically 25 or 42 bar)Mainly heat absorptionSuitable: design concentration below the NOAEL (9%), with alarm and evacuationHigh (HFC)Small
FK-5-1-12 (Novec 1230)Chemical clean agent (fluoroketone)Liquid, nitrogen-pressurized (25–50 bar)Mainly heat absorptionSuitable: design concentration below the NOAEL (10%), with alarm and evacuation1Small
IG-541 (Inergen)Inert gas (52% N₂, 40% Ar, 8% CO₂)Compressed gas (150, 200 or 300 bar at 15 °C)Oxygen dilutionSuitable: within the NFPA 2001 concentration and exposure-time limits≈0Large
IG-55 (Argonite)Inert gas (50% N₂, 50% Ar)Compressed gas (150, 200 or 300 bar at 15 °C)Oxygen dilutionSuitable: same NFPA 2001 limits as IG-5410Large
CO₂ (carbon dioxide)Carbon dioxideLiquefied, about 55–60 bar at room temperatureOxygen dilution (minimum 34% concentration)Not suitable: unoccupied or evacuated spaces only1Medium–large

The chemical clean agents (FM-200, FK-5-1-12) are also within the scope of the EU universal PFAS restriction proposal, which is still under assessment; details on our FK-5-1-12 page.

Which system could fit your project?

Answer four questions and we will show the system families that could fit, and why.

What needs protecting?
Are people present, or could they be?
How much room is there for cylinders?
Is a low global warming potential (GWP) a project criterion?

Systems worth considering

Answer the questions to see the result.

This pre-assessment does not replace the engineering calculation. The final choice depends on the volume, room integrity, the applicable standard and the system manufacturer's approvals.

Technical downloads

PDF documents for specification work, test preparation and product information.

All downloads →

Which gas suppression system suits which situation?

Gas suppression systems fall into two main families: inert gases (IG-541, IG-55), which extinguish by diluting oxygen, and chemical clean agents (FM-200, FK-5-1-12), which absorb heat and interrupt the combustion reaction. CO2 is a separate class used only in unoccupied spaces. These questions drive the choice:

  • Are people present? In server, archive or control rooms that staff enter, FM-200, FK-5-1-12 (Novec 1230) or IG-541 (Inergen) are preferred; CO2 is used only in unoccupied spaces or where evacuation is assured.
  • How much room is there for cylinders? Chemical clean agents protect the same volume with fewer cylinders; inert gases need more cylinders and a larger cylinder room.
  • Is environmental impact a priority? Inert gases and FK-5-1-12 (GWP 1) have very low impact; FM-200, as an HFC, has a high GWP.
  • Is it a room or a panel? If only a few critical electrical panels need protection, in-panel gas suppression stops the fire at its source.
  • Is detection in place? Every room system is designed together with a fire detection and control system that triggers the release.

Comparison guides

The final choice of agent is an engineering decision that weighs occupancy, room integrity, environmental priorities and the applicable standard. All system types, applications and project steps are brought together on our gas fire suppression systems home page.