Gas Fire Suppression Systems for Marine and Shipping

Gas fire suppression on ships puts out fires without water in enclosed spaces with limited escape routes, such as the engine room; an audible and visual alarm sounds before discharge, and the gas is released only after the time allowed for evacuating the space.

Our engineers respond within 24-48 hours.

Why Gas Suppression?

A ship’s engine room is an enclosed, confined space that combines fuel tanks, lubrication systems, and mechanical equipment running at high temperatures. A fire in this kind of confined space can grow quickly, and crew evacuation options are far more limited than at a shore facility — if a fire at sea cannot be brought under control, the entire vessel and crew are at risk. This is why gas suppression is a proven, standards-mandated method in maritime fire safety.

Water-based systems bring additional problems on board, including corrosion and added weight: contact between seawater or freshwater and metal surfaces in the engine room accelerates corrosion, and accumulated water can affect vessel stability. Gas systems avoid these risks while flooding the engine room to suppress fire uniformly throughout the space.

CO2 has historically been widely used in shipping, but its extinguishing concentration can be fatal if inhaled, so discharging it before evacuation is complete can have severe consequences. Inert gases such as IG-541 are applied at concentrations designed for spaces where people may be present, giving them a lower risk profile in an early or unintended discharge. Whichever agent is chosen, the SOLAS/FSS Code requires an alarm before release and the crew are expected to leave the space: a gas system is designed to extinguish the fire once the space has been cleared, not for crew to remain inside.

Sector-Specific Risks

Fuel and oil fires in the engine room can flash ignite the moment a leak or drip contacts a hot surface such as an exhaust manifold or turbocharger housing; these fires typically develop as a spreading pool fire, and conventional water application can even help spread them further. The confined-space layout compounds the danger for crew, since oxygen is limited and smoke fills the whole volume rapidly.

A ship at sea has no access to shore-based fire brigades or outside technical support, which means the vessel’s own suppression system is the only real line of defense when an incident occurs. This makes regular maintenance and verification of cylinder fill status far more critical than for a shore-based installation.

In spaces like the engine room, where crew may be present when an incident starts, agent selection should also consider the consequences of an early discharge; from that perspective inert gases such as IG-541 offer a lower risk profile than CO2. CO2 remains in use on many vessel types and in confined spaces managed under strict procedures. In either case, the pre-discharge alarm time, release controls and evacuation procedure must be designed to the FSS Code, and the choice evaluated together with the vessel’s classification society requirements and operating procedures.

The marine environment’s demanding conditions — vibration, humidity, and salt air — require equipment certified for maritime service, and detection systems must be calibrated to engine room ambient conditions to minimize false alarms. Thorough functional testing during commissioning carries even greater weight at sea than ashore, since an unexpected fault cannot be resolved once underway.

Typical fire hazards

#Hazard
1Fuel and oil-fed fires in the engine room
2Confined-space fire risk with limited means of escape
3Hot machinery surfaces and exhaust lines
4Corrosion and added weight concerns with water-based alternatives
5Limited maintenance and response capability at sea

Systems considered for this application

SystemAgent familyOccupied spaces
IG-541 (Inergen) Inert Gas Suppression SystemInert gas (52% N₂, 40% Ar, 8% CO₂)Suitable: within the NFPA 2001 concentration and exposure-time limits
CO2 Gaseous Fire Suppression SystemCarbon dioxideNot suitable: unoccupied or evacuated spaces only
Fire Detection Systems——

Frequently asked questions

Which gas carries lower risk in an engine room where evacuating the crew may take time?
CO2 at its extinguishing concentration can be fatal if inhaled, whereas inert gases such as IG-541 are applied at concentrations designed for spaces where people may be present. That gives inert gases a lower risk profile if an early or unintended discharge occurs. No agent replaces evacuation, however: under SOLAS, the FSS Code requires an audible and visual alarm before release into spaces where personnel normally work or have access, operating for the time needed to evacuate the space and in no case less than 20 seconds. Agent selection should be approved by the vessel's classification society.
Why is CO2 considered risky on ships if it's still used in shipping at all?
CO2 remains in use on many vessel types and in confined spaces managed under strict procedures, but discharging it before evacuation is confirmed can be fatal. Pre-discharge alarms, controlled release arrangements and headcount procedures are therefore critical for CO2 systems, and inert gas alternatives are also evaluated for spaces where crew are likely to be present during an incident.
Does gas suppression cause corrosion or affect the ship's stability the way water-based systems might?
No — that's part of why gas is preferred at sea. Seawater or freshwater contact with engine room metal accelerates corrosion, and accumulated water can affect vessel stability, risks that gas systems avoid entirely while still flooding the space uniformly.
How is the system kept reliable when there's no shore-based fire brigade or technical support once the ship is underway?
Because the vessel's own system is the only real line of defense at sea, regular maintenance and verification of cylinder fill status matter more than on a shore-based installation, and thorough functional testing during commissioning is emphasized precisely because a fault can't be resolved once underway.
Does the equipment need special certification for the marine environment?
Yes — vibration, humidity, and salt air require equipment certified for maritime service, and detection systems need to be calibrated to engine room ambient conditions to avoid false alarms, which is also why the choice of agent and configuration should be evaluated against the vessel's classification society requirements.

GYS is an Istanbul-based gas fire suppression company that runs the whole process in facilities like these with its own team, from survey to maintenance. Agent options and project steps are on our home page.

Sources

  1. IMO FSS Code (Res. MSC.98(73)), Chapter 5, para. 2.1.3.2 — pre-discharge alarm, at least 20 s

Let's choose the right system for your facility

List the rooms to protect and their approximate size. We select the agent by engineering calculation, based on occupancy, space and room integrity.